Detailing provisions
Columns
Longitudinal reinforcement
Stirrups (links)
Beams
Longitudinal reinforcement
Min bar distance |
The minimum clear distance between individual bars (for Design and Drawing). ÖNORM B 4700, Art. 5.2(2) Default value = 20 mm |
Max. bar distance |
The maximum clear distance between individual parallel bars (for Design and Drawing). Default value = 300 mm |
Stirrups (links)
Maximum transverse distance between stirrups |
The maximal transverse spacing of legs must not exceed 800 mm or d. ÖNORM B 4700: Art. 3.4.4.2(11) |
Maximum longitudinal spacing of stirrups |
The maximal longitudinal spacing of successive links is related to the shear force (Vsd). ÖNORM B 4700: Art. 3.4.4.2(11) |
Calculation (columns and beams)
This group contains switches for checks that can be applied during design and drawing of reinforcement.
Check min. bar distance |
Check for minimal distance of bars during design and drawing. |
Check max. bar distance |
Check for maximal distance of bars during design and drawing. |
2D Structures
Reinforcement
Min. transverse reinforcement percentage |
Minimal amount of transverse reinforcement, determined as a percentage of main reinforcement, Default value = 20%. |
Min. net reinforcement percentage (in general) |
Minimum percentage of longitudinal reinforcement, unconditionally. Default value = 0%. |
Shells and Walls only: If ON, the corresponding reinforcement is calculated automatically. ÖNORM B 4700: Art. 3.4.9.2, Eq. (60) |
|
Min pressure reinforcement percentage |
Shells and Walls only: Minimum part of concrete cross-section that should act as compression reinforcement. Default value = 0%. |
Maximum percentage inbending pressure zone |
Plates only: Definition of the maximum percentage of reinforcement in the bending pressure zone related to the concrete pressure force. Compare with SIA 162, Art. 3.24.16 Default value = 50%. |
Automatic calculation of minimum tension reinforcement |
If ON, the corresponding reinforcement is calculated automatically. ÖNORM B 4700: Art. 3.4.9.4(1), Eq. (61) |
Min tension reinforcement percentage on face+Zp |
Minimum percentage of tension reinforcement at the surface with positive Z co-ordinate (in the local coordinate system of the 2D member. Default value = 0%. |
Min tension reinforcement percentage on face–Zp |
Minimum percentage of tension reinforcement at the surface with negative Z co-ordinate (in the local coordinate system of the 2D member) or at each of the Wall faces, respectively. . Default value = 0%. |
Max reinforcement percentage in cross-section |
Maximal part of concrete cross-section that should act as reinforcement. ÖNORM B 4700: Art. 3.4.9.2 and/or Art. 3.4.9.3 Default value = 8%. |
Automatic calculation of min shear reinforcement |
If ON, the corresponding reinforcement is calculated automatically. ÖNORM B 4700, Art. 3.4.9.4(2), Eq. (62) |
Min shear reinforcement |
Minimal part of concrete cross-section that should act as shear reinforcement. Default value = 0.11%. |
Special program restriction
Virtual strut reduction factor |
It considers the diminished actual concrete strength in a 2D cracked continuum. Values lower or equal to 100 are valid only. (100 % = full concrete strength). |