Load case combinations for fire resistance calculations
With regard to the fire resistance calculations there are certain limitations and assumptions concerning load case combinations.
Fire resistance – detailing provisions
For Type of calculation = "Input by user" and "Automatic" all types of load cases/combinations/ classes can be used.
For Type of calculation = "from temp. curves" an accidental combination must be created:
-
EN-ULS Accidental – Psi1,
-
EN-ULS Accidental – Psi2.
Simplified method
This type of calculation is supported only for accidental combinations:
-
EN-ULS Accidental – Psi1,
-
EN-ULS Accidental – Psi2.
Remarks
-
For detailing provisions (Type of calculation = "from temp. curves") and for simplified calculation (check response and check capacity) only accidental combinations (EN-ULS Accidental – Psi1 and EN-ULS Accidental – Psi2 can be used,
-
Temperature curves can be defined only in a load case with action type = "accidental".
-
A load case with action type = "accidental" in an accidental combinations is in all linear combinations that will be generated from these accidental combinations.
-
Only one load case with action type = "accidental" can be in one accidental combination.
-
If an accidental combination without load case with action type = "accidental" appears in checks of fire resistance, the Document will contain an error message.
Advanced calculation
-
Only nonlinear combinations are supported.
-
There is a combo box Fire type in the dialog for the definition of a nonlinear combination:
-
-
prefire,
-
during fire,
-
post fire.
-
-
For this calculation new types of nonlinear combinations have to be generated
-
-
Prefire,
-
During fire ,
-
Post fire.
-
-
These nonlinear combinations are available only if functionalities Fire resistance (of concrete) and Physical non-linearity for reinforced concrete are turned on in the Project data dialogue.
-
If type of combination = "prefire" and a nonlinear combination contains a load case of type "Temperature distribution curves", then such a load case is ignored in the calculation.
-
If type of combination = "post fire" and a nonlinear combination contains a load case of type "Temperature distribution curves" , then such a load case is ignored in the calculation.
-
If type of combination = "during fire" and a nonlinear combination does not contain a load case of type "Temperature distribution curves", then a warning is issued that: "The nonlinear combination does not contain load case of type "Temperature distribution curves"".
-
If type of combination = "during fire" and a nonlinear combination contains more than one load case of type "Temperature distribution curves" , then a warning is issued that: "The nonlinear combination contains several load cases of type "Temperature distribution curves"".