Sliding check

The Sliding check is executed according to EN 1997-1 art. 6.5.3 [Ref.1]

The Sliding resistance Rd depends on the fact if the soil condition is drained or undrained.

The value Rp,d specifies the positive effect of the earth pressure at the side of the foundation. Since this effect cannot be relied upon, this value is taken as zero [Ref.2].

The sliding resistance is dependent on the condition of the subsoil.

  1. In case the Type field in the Subsoil Library is set to Undrained.

    Value Formula
    cud

    As specified in "Determination of Design Values"

    A'

    Effective area as defined in "Determination of Effective Geometry"

    Resistance factor read from the National Annex Setup


    In case the checkbox Water/air in clay subgrade in the Subsoil Library is activated, the value of Rdis limited as follows:

    Value Formula
    Vd As specified in "Determination of Effective Geometry"
  2. In case the Type field in the Subsoil Library is set to Drained.


    Value Formula
    Vd As specified in "Determination of Effective Geometry"
    Design friction angle at the foundation base.
    Dependent on the Cast condition specified in the Pad Foundation Library:

    Cast Condition
    Prefabricated
    In situ

    As specified in "Determination of Design Values"
    Resistance factor read from the National Annex Setup